Mitsubishi Inverter

Christian edited this page Feb 4, 2026 · 2 revisions

117 N020 PU Communication Station

Range: 00 to 31
Specify the inverter station number.
Enter the inverter station numbers when two or more inverters are connected to one personal computer.

118 N021 PU Communication Speed

Options: 192, 48, 96, 192, 384, 576, 768, 1152
Select the communication speed.
The setting value × 100 equals the communication speed.
For example, enter 192 to set the communication speed of 19200 bps.


119 PU Communication Stop Bit Length / Data Length

Stop Bit Length

  • 01 bit
  • 12 bits

Data Length

  • 107 bits
  • 118 bits

Parity Check

  • 0Without parity check
  • 1With parity check at odd numbers
  • 2With parity check at even numbers

120 N024 PU Connector Communication

  • 0PU connector communication is disabled

122 N026 PU Communication Check Time Interval

Range: 0.1 to 999.8 s
Set the interval for the communication check (signal loss detection) time.
If a no-communication state persists for longer than the permissible time, the inverter output will be shut off.

  • 9999No communication check (signal loss detection)

343 N080 Communication Error Count

Displays the communication error count during MODBUS RTU communication. (Read-only.)


549 N000 Protocol Selection

  • 0Mitsubishi inverter protocol (computer link)
  • 1MODBUS RTU protocol

Communication Specifications

  • The communication specifications are given below.
Item Description Related Parameter
Communication protocol MODBUS RTU protocol Pr.549
Conforming standard EIA-485 (RS-485)
Number of connectable units 1: N (maximum 32 units), setting is 0 to 247 stations Pr.117
Communication speed Selected among 300/600/1200/2400/4800/9600/19200/38400/57600/76800/115200 bps Pr.118
Control procedure Asynchronous method
Communication method Half-duplex system
Communication specifications
Character system Binary (fixed at 8 bits)
Start bit 1 bit
Stop bit length Select from the following three types: Pr.120
- No parity check, stop bit length 2 bits
- Odd parity check, stop bit length 1 bit
- Even parity check, stop bit length 1 bit
Parity check CRC code check
Error check CRC code check
Terminator Not available
Time delay setting Not available

Message frames comprise four message fields shown above.
A slave recognizes message data as one message when a 3.5 character long no-data time (T1: start/end) is added before and after the data.


Message Frame Structure

Start Address Function Data CRC Check End
T1 8 bits 8 bits n × 8 bits L 8 bits, H 8 bits T1

Message Field Descriptions

Address Field

  • "0 to 247" can be set in the 8-bit length field.
  • Set "0" for broadcast messages (instructions to all addresses).
  • "1 to 247" for individual slave messages.
  • The slave response also contains the address set by the master.
  • The value set in Pr.117 PU communication station number is the slave address.

Function Field

  • "1 to 255" can be set as the function code (8-bit).
  • The master sets the function to be sent to the slave, and the slave performs the requested operation.
  • An error response is generated if an unsupported function code is used.
  • The normal response contains the function code set by the master.
  • Error response contains H80 + function code.

Data Field

  • The format varies depending on the function code.
  • Example: Byte count, number of bytes, accessing content of holding registers.

CRC Check Field

  • Detects errors in the received message frame.
  • Errors are detected in the CRC check, and the 2 bytes of CRC data are appended to the message.
  • Order: Lower byte first, then upper byte.
  • Process:
    • The sender calculates and appends the CRC.
    • The receiver recalculates the CRC while receiving the message.
    • If the calculated CRC and received CRC do not match, an error is returned.

Inverter settings

Motor Constants

The following is a table that shows which Registers need to be set on the Inverter for the safe operation of the Motor.

Parameter number (Pr) Name Value
71 Applied Motor 0
80 Motor Capacity 15 (1.5 kw)
96 Auto tuning setting/status 1
1 Max Frequency 5000
2 Min Frequency 0
9 Electronic Thermal O/L Relay 3.30 (Ampere)
3 Base frequency 5000 (50 Hz)
19 Base frequency voltage 400 (Volt)

All Settings needed for the Inverter Communication/Operation with Extruder

The Following settings are required to get the inverter Communication and Operation working properly

Parameter Number (Pr) Value Description
Pr. 78 0 Allows Reverse Rotation
Pr. 79 0 Operation Mode Selection
Pr. 117 1 Station Number (Slave Number)
Pr. 118 192 Baudrate (192 → 19200 bps)
Pr. 119 0 Stop Bit Length
Pr. 120 2 Parity Check
Pr. 121 9999 PU communication retry count
Pr. 122 1.0 Communication Check Time (Time until no communication causes E.PUE fault), 0.1 seconds steps
Pr. 338 0 Communication operation command source, 0 -> given through PU
Pr. 339 0 Communication speed command source, 0 -> given through PU
Pr. 340 1 Startup in Network Mode
Pr. 549 1 Protocol Selection (1 = Modbus)
Pr. 551 9999 Automatically Detect PU Connector