Range: 00 to 31
Specify the inverter station number.
Enter the inverter station numbers when two or more inverters are connected to one personal computer.
Options: 192, 48, 96, 192, 384, 576, 768, 1152
Select the communication speed.
The setting value × 100 equals the communication speed.
For example, enter 192 to set the communication speed of 19200 bps.
-
0→ 1 bit -
1→ 2 bits
-
10→ 7 bits -
11→ 8 bits
-
0→ Without parity check -
1→ With parity check at odd numbers -
2→ With parity check at even numbers
-
0→ PU connector communication is disabled
Range: 0.1 to 999.8 s
Set the interval for the communication check (signal loss detection) time.
If a no-communication state persists for longer than the permissible time, the inverter output will be shut off.
-
9999→ No communication check (signal loss detection)
Displays the communication error count during MODBUS RTU communication. (Read-only.)
-
0→ Mitsubishi inverter protocol (computer link) -
1→ MODBUS RTU protocol
- The communication specifications are given below.
| Item | Description | Related Parameter |
|---|---|---|
| Communication protocol | MODBUS RTU protocol | Pr.549 |
| Conforming standard | EIA-485 (RS-485) | — |
| Number of connectable units | 1: N (maximum 32 units), setting is 0 to 247 stations | Pr.117 |
| Communication speed | Selected among 300/600/1200/2400/4800/9600/19200/38400/57600/76800/115200 bps | Pr.118 |
| Control procedure | Asynchronous method | — |
| Communication method | Half-duplex system | — |
| Communication specifications | ||
| Character system | Binary (fixed at 8 bits) | — |
| Start bit | 1 bit | — |
| Stop bit length | Select from the following three types: | Pr.120 |
| - No parity check, stop bit length 2 bits | ||
| - Odd parity check, stop bit length 1 bit | ||
| - Even parity check, stop bit length 1 bit | ||
| Parity check | CRC code check | — |
| Error check | CRC code check | — |
| Terminator | Not available | — |
| Time delay setting | Not available | — |
Message frames comprise four message fields shown above.
A slave recognizes message data as one message when a 3.5 character long no-data time (T1: start/end) is added before and after the data.
| Start | Address | Function | Data | CRC Check | End |
|---|---|---|---|---|---|
| T1 | 8 bits | 8 bits | n × 8 bits | L 8 bits, H 8 bits | T1 |
-
"0 to 247"can be set in the 8-bit length field. - Set
"0"for broadcast messages (instructions to all addresses). -
"1 to 247"for individual slave messages. - The slave response also contains the address set by the master.
- The value set in Pr.117 PU communication station number is the slave address.
-
"1 to 255"can be set as the function code (8-bit). - The master sets the function to be sent to the slave, and the slave performs the requested operation.
- An error response is generated if an unsupported function code is used.
- The normal response contains the function code set by the master.
-
Error response contains
H80+ function code.
- The format varies depending on the function code.
- Example: Byte count, number of bytes, accessing content of holding registers.
- Detects errors in the received message frame.
- Errors are detected in the CRC check, and the 2 bytes of CRC data are appended to the message.
- Order: Lower byte first, then upper byte.
-
Process:
- The sender calculates and appends the CRC.
- The receiver recalculates the CRC while receiving the message.
- If the calculated CRC and received CRC do not match, an error is returned.
The following is a table that shows which Registers need to be set on the Inverter for the safe operation of the Motor.
| Parameter number (Pr) | Name | Value |
|---|---|---|
71 |
Applied Motor | 0 |
80 |
Motor Capacity | 15 (1.5 kw) |
96 |
Auto tuning setting/status | 1 |
1 |
Max Frequency | 5000 |
2 |
Min Frequency | 0 |
9 |
Electronic Thermal O/L Relay | 3.30 (Ampere) |
3 |
Base frequency | 5000 (50 Hz) |
19 |
Base frequency voltage | 400 (Volt) |
The Following settings are required to get the inverter Communication and Operation working properly
| Parameter Number (Pr) | Value | Description |
|---|---|---|
Pr. 78 |
0 | Allows Reverse Rotation |
Pr. 79 |
0 | Operation Mode Selection |
Pr. 117 |
1 | Station Number (Slave Number) |
Pr. 118 |
192 | Baudrate (192 → 19200 bps) |
Pr. 119 |
0 | Stop Bit Length |
Pr. 120 |
2 | Parity Check |
Pr. 121 |
9999 | PU communication retry count |
Pr. 122 |
1.0 | Communication Check Time (Time until no communication causes E.PUE fault), 0.1 seconds steps |
Pr. 338 |
0 | Communication operation command source, 0 -> given through PU |
Pr. 339 |
0 | Communication speed command source, 0 -> given through PU |
Pr. 340 |
1 | Startup in Network Mode |
Pr. 549 |
1 | Protocol Selection (1 = Modbus) |
Pr. 551 |
9999 | Automatically Detect PU Connector |
QiTech Control | GitHub | Video Demo | Open Source Framework for Industrial Control
- Getting Started
- Adding a Machine
- Adding a minimal machine e.G. 4CH DO
- Code Style
- Performance
- Testing
- Adding Presets to Machines
- NixOS
Beckhoff:
WAGO:
- 4 Digital In (750-402)
- 8 Digital In (750-430)
- 8 Digital In + 8 Digital Out (750-1506)
- 4 Analog In (750-455)
- 2 Digital Out (750-501)
- 8 Digital Out (750-530)
- Stepper (750-671 & 750-672)
- Power Supply (2789‐9052)
- Serial Interface (750-652)
- 4-channel Analog input module Pt100 RTD (750-460)
- 8 Digital In + 8 Digital Out (750-430 + 750-530)
Elrest:
WAGO: